Re: UK Pole Xfmr Question
Tesla List wrote:
> Original Poster: "Gregory R. Hunter" <ghunter-at-enterprise-dot-net>
>
> While preparing my 5KVA pole pig for shipment to the US, I realized I don't
> know enough about it. It has six external ceramic insulators--four for
> 240V and two for 11KV. Why does it have four 240V bushings? should I use
> two on the same side, or one from each side, or all four somehow? Anyone
> who understands how to properly connect this thing to 240V please respond
> on or off list. Many thanks.
The 4 smaller terminals are for the 240V and the + and - 5% taps, normally
you should connect one from each side ( I use a1 and a4 as this gives the
highest output voltage). The faceplate should give details of which
connections
are for what taps.
--
**********************************************************************