Re: Wiring suggestions
Original poster: "Jim Lux" <jimlux-at-earthlink-dot-net>
----- Original Message -----
From: "Tesla list" <tesla-at-pupman-dot-com>
To: <tesla-at-pupman-dot-com>
Sent: Saturday, May 22, 2004 3:41 PM
Subject: Re: Wiring suggestions
> Original poster: "Harold Weiss" <hweiss-at-new.rr-dot-com>
>
> Hi Eric,
>
> You would want at least 10 gauge wire for 30A. 10/4 SOW cable can be
bought
> at most home improvement stores. The black and red are your hot leads,
with
> the white being neutral and the green ground. Preferably go with 30A
twist
> lock connections, as the 30A dryer plugs aren't the safest things to
unplug
> if the line is hot. (too easy to get fingers into the prongs)
>
>
And PLEASE, use the right plug configuration for that wiring configuration
(single phase, 125/250, 3 pole, 4 wire)
There's a straight blade configuration (with 4 prongs) for 30A -NEMA 14-30P,
Hubbell HBL9431C, for example
And there's a twist lock configuration L14-30P
If you're not using the neutral (240V only) there are plugs for that
configuration as well...NEMA 6-30P for instance, or
L6-30P for locking
http://www.leviton-dot-com/sections/techsupp/nema.htm shows the straightblade
configurations